Product
Crucial Power Systems ES1.5A0100N1-S
Category
Electronics
Report number
20191217-DF529-2147375971
Ownership age
Not stated
Failure type
Stopped working / malfunction
Incident narrative
SaferProducts.gov consumer incident report 20191217-DF529-2147375971. Severity: Incident, No Injury. Product: Crucial Power Systems ES1.5A0100N1-S (Crucial Power Systems - Emergency Power System). Incident: Crucial Power Systems Model ES1.5 A0100 N1-S S/N ES1562 This is an emergency lighting system designed to provide emergency egress lighting in the event of a utility power failure. The equipment consists of a power inverter, controller, touch screen control/monitor and batteries contained in a cabinet. The system uses one 120V AC circuit for input power and distributes output power to up to six 120V circuits. In the event of a utility power failure the system is designed to provide un-interrupted output power for egress lighting for a minimum of 90 minutes to be in compliance with current life safety codes. This particular system failed recently and shutdown output power to the egress lighting throughout the building. The lights were out until an electrician got to the site and temporarily bypassed the system and directly connected the loads to the line feed. Under certain circumstances this could be a hazardous situation. The building egress path was completely in the dark. The system should either fail to "lights on" or be provided with a bypass switch as a standard feature. The bypass switch is offered as an option.
Official report number: 20191217-DF529-2147375971. Search that ID on SaferProducts.gov or match it in the CPSC public database export to verify this record.